NEW FACILITIES
The minimum volume for a gravity two-compartment grease interceptor is 800 gallons and must service the entire commercial kitchen. No single point of use pretreatment device will be allowed. The volume of an adequately sized solids and/or grease interceptor (GI) to handle the non-domestic waste stream originating from a commercial kitchen such as a restaurant is primarily based on the number of seats where meals are served (meal production), the type of food items presented on the menu and the number and type of each cooking appliance to be installed in the kitchen. The plumbing plans for establishments with commercial kitchens must show all plumbing fixtures and drains that are within the vicinity of cooking equipment in the food prep, cookline and ware washing areas of the kitchen being routed to the interceptor. Areas of the establishment that are outside the commercial kitchen where no solids/grease waste is generated i.e. bars, beverage stations, wait stations, restroom, etc. are routed directly to the building domestic sanitary waste system.
Additional notes and guidance on the information to provide for the calculated sizing of the interceptor can be found on the GI sizing calculator cover page. Locations with existing interceptors will be required to have it inspected for condition and size prior to approval.
Retail/Wholesale Food Establishment Application(PDF, 563KB)
Grease Interceptor Sizing Worksheet(XLSM, 153KB)
(Requires Microsoft Excel Version 2003 or later)
Grease Interceptor Sizing Criteria(PDF, 136KB)
*Updates as follows since date of approved document GI Requirements Update P-400-501
- Any use of the referenced UPC Appendix H is for variance requests only.
- See Building Codes, Policies and Guides page for the current adopted I-Codes and Denver Building Code amendments.
The City and County of Denver utilizes the two-compartment gravity grease interceptor which can be found under our Standards and Details Tab below. All projects are required to use the standard two-compartment concrete detail and is to be added to your plans submitted for review.
Any deviation from the standard detail is subject to further review and approval from the DOTI Wastewater Variance Committee. To request a variance, please provide the following in your initial submittal or resubmittal:
- A completed variance application(PDF, 269KB).
- A letter signed by the owner outlining the reasons for the request. Please note that cost is not a hardship.
- Any additional plans or documents supporting your request.
A formal letter of approval or denial will be emailed to the owner from your reviewer after review of the variance request. Variances are reviewed by the committee weekly and are responded to within one week of decision.
For those kitchen facilities that generate no or minimal amounts of grease/solid waste, a variance to a grease interceptor may be granted by the plan reviewer at their own discretion. Your reviewer will determine if you qualify for an automatic variance during review. Possible examples include facilities that serve prepackaged food, drinks, etc. for sale or consumption.
EXISTING FACILITIES
Every existing establishment with a commercial kitchen undergoing a change in the mode of operation will include a pre-treatment device review to provide adequate protection to the public sanitary sewer system from solids and/or grease waste accumulation based on the following scope of work modifications to the existing establishment:
- ownership
- business name
- process (preparation and cooking)
- menu
- seating capacity
- additional or change in equipment and/or space
The existing facilities will undergo the same reviews as noted above for new establishments. Location with existing interceptors will be required to have it inspected for condition and size prior to approval.